VENKO Sp. z o.o.
https://venko.com.pl/en/produkt/lpt-1-lightning-protection-tester/
Export date: Fri Apr 26 5:13:08 2024 / +0000 GMT



LPT-1 Lightning Protection Tester

Price: netto

Product Categories:

Product Page: https://venko.com.pl/en/produkt/lpt-1-lightning-protection-tester/

 

Product Summary

The Lightning Protection Tester LPT-1 is used to diagnose the state of grounding devices, and is intended for measurements in order to determine the impulse resistance of grounding conductors of high-voltage line supports and stand-alone lightning conductors.

Product Description

The Lightning Protection Tester LPT-1 is used to diagnose the state of grounding devices, and is intended for measurements in order to determine the impulse resistance of grounding conductors of high-voltage line supports and stand-alone lightning conductors.

The Lightning Protection Tester LPT-1 is a portable equipment that generates voltage and current pulses of aperiodic form with given amplitude-time parameters and measures the amplitude values of voltage and current pulses.

Characteristics

Value

1. The shape of the generated voltage and current pulses

aperiodic

2. Polarity of the generated voltage pulses

positive

3. Maximum amplitude of generated voltage pulses in idle mode, V

1000 ± 200

4. Duration of the front of the generated voltage pulses at idle (at levels of 0.1-0.9 of amplitude), μs

1,2 ± 0,1

5. The pulse duration of the generated voltage pulses at idle (at a level of 0.5 of amplitude), μs

50 ± 5

6. Measuring ranges of amplitudes of voltage pulses, V

              – range 5

              – range 50

              – range 500

 

от 0,5 до 5

от 5 до 50

от 50 до 500

7. The limit of the permissible value of the relative error of measurement of the amplitudes of the voltage pulses,%, not more

± 10

8. The maximum amplitude of the generated current pulses in the short circuit mode to the output, A

20 ± 5

9. The duration of the front of the generated current pulses in the short circuit mode (at levels of 0.1-0.9 of amplitude), μs

8 ± 0,8

10. The pulse duration of the generated current pulses in the short circuit mode (at a level of 0.5 of amplitude), μs

20 ± 4

11. The measurement range of the amplitude of the current pulses under load from 1 Ω to 600 Ω, A

from 1 to 25

12. The limit of the permissible value of the relative error of measurement of the amplitude of current pulses,%, not more

± 10

13. Power consumption, W, not more than

40

14. Dimension, mm

           – voltage and current pulse generator GINT

              – voltage pulse meter VPM

370×350×170

170×90×55

15. Weight, kg

10

 

Product added date: 2019-02-09 19:59:14
Product modified date: 2024-03-07 21:56:11

Export date: Fri Apr 26 5:13:08 2024 / +0000 GMT
Product data have been exported from VENKO Sp. z o.o. [ https://venko.com.pl ]
Product Print by WooCommerce PDF & Print plugin.