High current testing device HCTD-20M (20kA)

Price: netto

Product Categories:

Product Tags: , , , ,

Product Page: https://venko.com.pl/en/produkt/high-current-testing-devices-hctd-20ka/

 

Product Summary

High current testing device HCTD-20M designed for testing ampere-second characteristics of circuit breakers by AC current at 50 Hz frequency up to 20 kA.

Product Description

High current testing device HCTD-20M designed for testing ampere-second characteristics of circuit breakers by AC current at 50 Hz frequency up to 20 kA.

Devices allow registering the value of output current and timing the automatic circuit breaker switching interval.

Also devices may be used as an adjustable AC current source up to 20 kA for power circuits with low impedance.

 

Supply voltage (50 Hz ±1 Hz) 230V ± 10%; 380 ± 10%
Maximum output voltage 7 V (50 Hz)
Maximum RMS output current
(230 V supply voltage)
13,0 kA
Maximum RMS output current
(380 V supply voltage)
20,0 kA
Output current measuring range (“A” mode) 10 А - 1000 А
Output current measuring range (“kA” mode) 20 A - 20 kA
Power consumption, max 55 kVA
Test current duration measuring range 50 ms - 990 ms;
1 s - 7200 s
Current measuring accuracy 1,5 % of range
Duration measuring accuracy 3 % odczytu
Max. testing duration at max. output current 10 s
Weight (without busbars) 86 kg
Dimensions 1097x650x870 mm
Busbars S=110 mm2, l=1 m 8 szt.

 

 

 

 

 

 

 

 

 

 

 

 

 

High Current Test Device HCTD-20M provide a short duration output through a typical circuit breaker when an instantaneous trip element must be tested.

Sufficient current is available for testing time delay characteristics of motor overload relays and circuit breakers.

The intuitive control makes the test set easy to operate.

Sensing leads, which operate on either normally-open or normally-closed devices, are connected to the test object auxiliary contacts or open breaker pole. The output current level can be easily preset.
When the output is initiated, the preset output current locks on and the timer starts. When the test set senses a change in state of the test object auxiliary contacts (NO to NC or NC to NO), the current shuts off and the timer stops.

High current device HCTD-20M can be used as a universal current source up to 20kA.

 

Product Gallery

 High current testing device HCTD-20M  High current testing devices HCTDHigh current testing devices HCTD-20M with Rectifier RS-6 

 

Product added date: 2017-11-27 20:51:42
Product modified date: 2024-03-03 21:33:31

Export date: Thu Apr 18 11:25:26 2024 / +0000 GMT
Product data have been exported from VENKO Sp. z o.o. [ https://venko.com.pl ]
Product Print by WooCommerce PDF & Print plugin.