Product Summary

High current testing device HCTD-14M is designed to test the ampere-second characteristics of circuit breakers (AC current, 50 Hz frequency, up to 14 kA).

Product Description

High current testing device HCTD-14M is designed to test the ampere-second characteristics of circuit breakers (AC current, 50 Hz frequency, up to 14 kA).

Device allow registering the output current and timing of automatic circuit breaker switch interval.

Besides, the devices may be used as adjustable AC source up to 14 kA for power circuits with low impedance.

Supply voltage (50 Hz ±1 Hz) 230V ± 10%; 380 ± 10%
Maximum output voltage 7 V (50 Hz)
Maximum RMS output current
(230 V supply voltage)
9,0 kA
Maximum RMS output current
(380 V supply voltage)
14,0 kA
Output current measuring range (“A” mode) 10 А - 1000 А
Output current measuring range (“kA” mode) 14 A - 14 kA
Power consumption, max 55 kVA

Measuring range of test current duration

50 ms - 990 ms;
1 s - 7200 s
Current measuring accuracy 1,5 % of the range

Measuring accuracy of duration

3 % of reading
Max. testing duration at max. output current 10 s
Weight (without busbars) 54 kg
Dimensions 450x250x475 mm
Busbars S=110 mm2, l=1 m 8 pcs.

High Current Test Device HCTD-14M ensures a short duration of output through typical circuit breaker when  instantaneous trip element must be tested.

Sufficient current is available for testing  the time delay characteristics of motor overload relays and circuit breakers.

Intuitive control ensures easy operation the test.

Sensing leads, which operate on either normally-open or normally-closed devices, are connected to test object auxiliary contacts or open breaker pole. Output current level can be easily preset.
When the output is initiated, preset output current locks on and the timer starts. When test kit senses the change in state of the test object auxiliary contacts (NO to NC or NC to NO), the current shuts off and the timer stops.

High current device HCTD-14M can be used as a universal current source up to 14kA.

 

Product added date: 2017-12-08 20:37:21